Archive for November, 2006
Water Underfloor Heating Pressure Testing
Before connecting the unit to the primary circuit it is recommended to pressure test the system.
This can best be achieved by connecting mains pressure hose to the red ball valve and a hose or
bucket to the blue ball valve on the control unit. Open both valves fully & fill the system to purge
all traces of air from the system.
After all the air has been removed it is recommended to pressure
test the system with 6 bar pressure for 24 hours. We recommend maintaining
the system under pressure whilst screeding.
Note
,
if there is a risk for the air temperature dropping below freezing, then you must protect the pipes
Installation of the Single Room Pack for Underfloor Heating
The Compact UFH System is designed for wall fixing and ideally should be
mounted in a horizontal position with the electrical connection box uppermost.
However, it can also be mounted vertical to pump up or down if desired.
Provision should be made to vent air to protect pump from cavitation.
The unit must not be floor mounted or in any position that inclines the pump shaft
vertical. Refer to the pump installation leaflet enclosed.
Choose the location for the unit ensuring adequate clearance and
accessibility
for pipework and any subsequent maintenance. This is particularly important
if
enclosed within a cupboard space for example.
Locate the unit on the wall and mark the hole fixing positions through the
bracket.
Take care to protect any electrical equipment and cables during handling.
When connecting the pipe to the manifold use the cutter supplied to cut the pipe square then
calibrate the cut end to round the pipe ready to accept the compression adaptor. As the adaptor has
integral ‘O’ rings it is not essential to use further sealant such as PTFE tape.
