Commisioning
 

Commisioning

The system must be filled with water and fully vented of air. This can be best achieved using mains pressure through the two filling valves at the end of the manifolds.

All valves should be closed and the flow filling valve connected with a hose to the mains water supply, with the return filling valve connected to a hose laid to a wastewater point.

One by one the flow and the return valves are opened and closed purging the loops of air. When this is completed and the filling valves closed off, the pumps should be run for five minutes and the air vented again at the air bleed valve on the filling valves until all air is bled from the system.

The manifolds are supplied with options for individual control for each room. On the return manifold (the blue caps), actuators can be mounted for individual control. If a programmable room thermostat with a two port valve is controlling the system and there is no individual control, the “blue caps” should be left open.

The flow manifolds are supplied with flow gauges. To adjust the flow gauges, us the key provided with the manifolds. See instructions included in the manifold box on how to adjust the flow meters.

The following is an approximate guide, as how far each loop should be adjusted;

Size of Loop

Percentage Open

10 – 30 metres

30 % open

40 – 60 metres

50 % open

60 – 90 metres

75 % open

90 – 100 metres

100 % open

If the return manifold is not getting warm, there is either air in the system or the mixing valve is mounted in the wrong direction. Check the position of the mixing valve and bleed the loops separately again while the system is running.

Testimonials

  • "We have used Underfloor Heating Systems Ltd on various projects from single extensions up to new build properties. Excellent service and quality goods with quick turnaround on prices and deliveries."

    Reg Sears RJS Builders Ltd

  • "To the guys at "Underfloor Heating Systems" thanks again for the fantastic service and delivery please feel free to use me as a reference for any future customer"

    Paul (self builder) in Scotland

  • "We work with Underfloor Heating Systems Ltd and we are always impressed with their high level of service"

    Mr R P, Worcestershire

  • "We have worked with Underfloor Heating Systems Ltd for many years now and we found them to be honest and ethical."

    Mr Clark, Managing Director, Scotland

  • "Underfloor Heating Systems Ltd have always provided a great service. Their prices are very competitive and they are very knowledgeable on the technical side of things. I wouldn't use anyone else."

    Phil K

  • "I've been installing underfloor heating for 6 years now and I always use Underfloor Heating Systems Ltd. I have done over 300 of their systems and never had any issues at all."

    Mr I C from Kent

  • "We have used Under Floor Heating Systems product on numerous projects and have found that the quality of product and service is excellent."

    Akhil Haria